Model
|
MIN
2500TL-X
|
MIN
3000TL-X
|
MIN
3600TL-X
|
MIN
4200TL-X
|
MIN
4200TL-X
|
MIN
4200TL-X
|
Input DC
|
||||||
Max. recommended PV power
(for module STC) |
3500W |
4200W
|
5040W
|
5880W
|
6440W
|
7000W
|
Max. DC voltage
|
500V
|
500V
|
550V
|
550V
|
550V
|
550V
|
Start voltage
|
100V
|
100V
|
100V
|
100V
|
100V
|
100V
|
MPPT voltage range(V) :
|
50V-450V
|
70V-450V
|
70V-450V
|
70V-450V
|
70V-450V
|
70V-450V
|
Nominal voltage
|
360V
|
360V
|
360V
|
360V
|
360V
|
360V
|
Max. input current
|
13.5A
|
13.5A
|
13.5A
|
13.5A
|
13.5A
|
13.5A
|
Max. input current per string
|
13.5A
|
13.5A
|
13.5A
|
13.5A
|
13.5A
|
13.5A
|
Number of independent MPP
trackers/strings per MPP tracker |
2/2
|
2/2
|
2/2
|
2/2
|
2/2
|
2/2
|
Output AC
|
||||||
Rated AC output power
|
2500W
|
3000W
|
3600W
|
4200W
|
4600W
|
5000W
|
Max. AC power
|
2500W
|
3000W
|
3600W
|
4200W
|
4600W
|
5000W
|
Max. output current
|
11.3A
|
13.6A
|
16A
|
19A
|
20.9A
|
22.7A
|
AC nominal voltage
|
220V/230V/240V
|
|||||
AC grid frequency; range
|
50Hz,60Hz /±5Hz
|
|||||
Adjustable power factor
|
0.8leading...0.8lagging
|
|||||
THDI
|
<3%
|
|||||
AC connection
|
Single phase
|
|||||
Efficiency
|
||||||
Max.efficiency:
|
98.4%
|
|||||
EU efficiency:
|
97.5%
|
|||||
MPPT efficiency :
|
99.9%
|
|||||
Protection
|
||||||
DC reverse polarity protection
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
DC switch
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Output over current protection
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Output AC overvoltage Protection
- Varistor |
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Ground fault monitoring
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Grid monitoring
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Integrated all-pole sensitive
leakage current monitoring unit |
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|